AC load bank 1.000kW VPR P380ABE500+ (2 module)
Automatic load bank 1 phase 220V or 3 phase 380V (max 450V) for test UPS, generator, transformer, … capacity from 5kW to 1.000kW. This 1.000 kVA load bank can operate in 2 types of controls automatically or manually (manual control mode). Load bank 1.000 kVA allow running load tests to check AC power in constant power mode(CP), constant current mode (CC) or constant resistor mode (CR)…
The load bank has a removable module design structure that allows the flexibility to upgrade 2 more module to increase the testing capacity of the AC power source up to 2.000kVA on the same system.
Load bank VPR P380ABE500+ ( 2 module/ 1.000kVA ) is used in the test cycle of backup UPS, backup generators in hydro power plants, thermal power plants, oil and gas rigs such as: Transformer UPS, Emergency Lighting UPS power, FGD UPS System, LP CO2 UPS System, AC/DC UPS Distribution System, AC/DC UPS Distribution… The corresponding 1.000 kW load bank is used for the following purposes:
Used to check power, current, frequency… as well as handle wet stacking of single-phase 220VAC (or 3-phase) generators with nominal capacity of 15kVA, 20kVA, 40kVA, 60kVA, 80kVA, 100kVA, 125kVA, 200kVA, 250kVA, 500kVA, 800kVA, 1.000kVA
Used to test power, current, frequency… single-phase 220VAC (or 3-phase) UPS rated capacity 15kVA, 20kVA, 40kVA, 60kVA, 80kVA, 100kVA, 125kVA, 200kVA, 250kVA, 500kVA, 500kVA, 800kVA, 1.000kVA
Used to test power, current, frequency… of inverter 1 phase 220VAC (or 3 phase) rated capacity 15kVA, 20kVA, 40kVA, 60kVA, 80kVA, 100kVA, 125kVA, 200kVA, 250kVA, 500kVA, 500kVA, 800kVA, 1.000kVA
Used to test the power, current, frequency… of single-phase 220VAC (or 3-phase) AC power supply rated capacity 15kVA, 20kVA, 40kVA, 60kVA, 80kVA, 100kVA, 125kVA, 200kVA, 250kVA, 500kVA, 500kVA, 800kVA, 1.000kVA
1 | Load bank product code | VPR P380ABE500+ (1.000A) |
---|---|---|
2 | Description | Load bank AC 1.000kw (2 module) |
3 | Brand | VIETPRO |
4 | Load bank typr | Hybrid |
5 | Nominal power discharge | 1.000kW |
6 | Nominal discharge current | 1.515A |
7 | Nominal voltage (1 phase) | 220VAC |
8 | Nominal voltage (3 phase) | 380VAC |
9 | Initial power upgrade on the same module | N/A |
10 | Power upgrade the system by expanding more module | Can be upgraded to 2MW by equipping 2 additional 0.5MW modules |
11 | auxiliary power supply | 80~220VAC |
12 | use main AC test source as auxiliary power | Option |
13 | Automatic operation | Yes |
14 | Built-in manual control | Yes |
15 | Operation modes | Constant power ( CP ), constant current ( CC )… |
16 | Move | 6 wheels combined with crane hook |
17 | Size (mm) | 2 x W1340 x H1770 x D1780 |
18 | Number of manual control switches | ≥13 |
19 | Number of automatic control switches | 24 |
20 | Computer connect port | Yes |
21 | Download datasheet load bank 1.000kVA | download catalogure |